We are specialized in execution glass fused to steel tanks in ovens with a temperature of 800 C, for drinking water, sewage water, fire water, petrol and chemicals.
The glass is fused with the steel sheet at very high temperature which gives the steel of the tank extra protection. The tank sheets are connected together at site by special type of bolts and sika on the required area and with proper height to achieve giant volumes up to 20,000 M3 of water.
Features
Samples of glass lined tanks
Technical specifications
Capacity
20 – 20,000 M3
Dimensions
4 to 58 m
Height
2.8 to 8.3 m approximate net height.
Bolts and fittings
Galvanized steel with plastic cap from outside the tank. Galvanized expansion bolts for the tank base
Roof
Corrugated sheets 0.5 mm thick or flat sheets Aluminum 1.5mm thick fixed on galvanized columns and ribs, with stainless steel expansion bolts
Stiffening angles
Top and bottom stiffening angle rings
Sealant
Mastic Sika
Design
UBC Seismic zone 0, and 100 mph wind speed or as required
Type
Vertical, Circular glass fused to steel panel, Bolted tank, for erection above ground on a concrete base
Accessories
Mg + Anode Cathode Protection for the roof. Internal galvanized plate flanges , safe cage ladder, Side maintenance manhole, and level meter gauge